Approval
|
UL 489
|
|
Type
|
Thermal Magnetic, Non-Interchangeable Trip
|
|
Frame Type
|
JD
|
|
Maximum AC Voltage Rating
|
600 Volt
|
|
Current Rating
|
300 Amp at 40 Deg C
|
|
Number of Poles
|
3
|
|
Terminal Type
|
Line and Load Lug
|
|
Model
|
JXD6-A
|
|
Size
|
7.5 Inch Width x 4 Inch Depth x 11 Inch Height
|
|
Voltage Rating
|
600 Volt AC, 500 Volt DC
|
|
Maximum DC Voltage Rating
|
500 Volt
|
|
Additional Information
|
Application Reverse Feed; Applicable Standard IEC 60947-2
|
|
Interrupting Rating
|
65 Kiloamp at 240 Volt AC, 35 Kiloamp at 480 Volt AC, 25 Kiloamp at 600 Volt AC (UL), 65/33 Kiloamp at 220/240 Volt AC, 40/20 Kiloamp at 380/415 Volt AC (IEC), 25 Kiloamp at 500 Volt DC
|