14JG32AA81
This product is not the latest and may have limited availability.
Please chat with one of our Control Systems experts to discuss your needs.
Non-reversing motor starter, Size 4, Three phase full voltage, Amb. compensate bimetal OLR, Contactor amp rating 135A, 110 120/220 240VAC 60Hz coil, Non-combination type, Enclosure type (open), No enclosure
Due to supply constraints, inventory may be reserved for critical needs with contract customers. Please contact our chat team for assistance.
Product Details
Size
|
NEMA 4
|
Enclosure Type
|
Open
|
Construction Standard
|
NEMA
|
Type
|
Non-Reversing
|
Power Rating/Voltage
|
40 HP at 200/208 VAC, 50 HP at 220/230 VAC, 100 HP at 460/480/575/600 VAC, 600 VAC at 60 Hz
|
Current Rating
|
135 Ampere
|
Phase
|
3
|
Overloads
|
Ambient Compensated Bimetal Overload Relay, Automatic/Manual Reset, Class 14, Thermal Overload Current Setting Range 0.85 to 1.15 Ampere
|
Additional Information
|
Overall Dimension 6.75 Inch W x 5.75 Inch D x 12.4 Inch H; Number of Poles 3; Terminal Type Box Lug; Mounting Position Vertical; Mounting Type Surface; Operating Temperature -20 to 40 Deg C; Approval UL, CSA
|
Auxiliary Contact
|
1NO
|
Motor FLA
|
0.85 to 1.15
|
Coil Voltage
|
110 to 120/220 to 240 VAC at 60 Hz
|